Low voltage circuit breakers

Updated 2026-10-27

Data records

  • Chapter 15 of NFPA 70B-2026 covers low- and medium-voltage circuit breakers; section 15.3 holds the periodic maintenance procedures for molded-case, insulated-case and low-voltage power circuit breakers, and section 15.4 those for medium-voltage power circuit breakers. Source: NFPA 70B-2026, clause Chapter 15. Verified 2026-10-27. Record equip.low-voltage-circuit-breakers.nfpa70b.chapter
  • Table 15.3.5 of NFPA 70B-2026 lists the electrical tests for molded-case, insulated-case and low-voltage power circuit breakers, among them infrared thermography, contact resistance, insulation resistance, trip-unit calibration, inverse-time and instantaneous trip tests, rated hold-in, millivolt drop and, where applicable, arc reduction technology. Source: NFPA 70B-2026, clause Table 15.3.5. Verified 2026-10-27. Record equip.low-voltage-circuit-breakers.nfpa70b.electrical-tests

Sources

  • NFPA 70B-2026, Standard for Electrical Equipment Maintenance, 2026 edition, NFPA. Cited: clause Chapter 15; clause Table 15.3.5. Held as: Purchased single-user copy.